Informacja

Drogi użytkowniku, aplikacja do prawidłowego działania wymaga obsługi JavaScript. Proszę włącz obsługę JavaScript w Twojej przeglądarce.

Tytuł pozycji:

Quick-response protection system against electric shock in distributed generation systems

Tytuł:
Quick-response protection system against electric shock in distributed generation systems
Autorzy:
Shkrabets, Fedir
Plaksin, Sergej
Ostapchuk, Oleksandr
Kuznetsov, Valeriy
Tymchenko, Irina
Muntian, Antonina
Data publikacji:
2021
Wydawca:
Polska Akademia Nauk. Polskie Towarzystwo Diagnostyki Technicznej PAN
Tematy:
electric networks
protection
reliability
ground fault current
electrical safety
protection against electric shock
signal processing system
analog filtering
sieci elektryczne
ochrona
niezawodność
bezpieczeństwo elektryczne
ochrona przeciwporażeniowa
system przetwarzania sygnału
filtracja analogowa
Źródło:
Diagnostyka; 2021, 22, 3; 59-65
1641-6414
2449-5220
Język:
angielski
Prawa:
CC BY: Creative Commons Uznanie autorstwa 3.0 Unported
Dostawca treści:
Biblioteka Nauki
Artykuł
  Przejdź do źródła  Link otwiera się w nowym oknie
The peculiarities of the operation of distributed generation systems lead to a change in the requirements for the reliability and safety of the power distribution systems in which they are integrated. To meet the increased requirements, continuous monitoring of the insulation parameters (active resistance and capacitance to ground) is often used with operating artificial non-industrial frequency operational signals introduced into the network. In the case of a sudden touch, such a system is not effective, since the response time of the protection device, which consists of the signal processing time and the operating of the actuator, is crucially important. For the used operational signals with a frequency of 100 and 200 Hz, the processing time using the Fourier transform is 10 ms for 100 Hz and 5 ms for 200 Hz. Considering that the response time of the fastest actuators (based on vacuum switches) is from 3 to 7 ms, this is a rather significant period of time. To develop an effective resolver system, the capabilities of the Matlab environment were used to determine the most successful design of an analog prototype (Butterworth, Bessel, Chebyshev and Cauer of 6th order) for an operational signal with a frequency of 200 Hz. As a result, the processing time was established, which varies widely from 3.5 to 19 ms. Taking into account the known indicators, namely the frequency and number of operational signals, a signal processing system was developed using the vector-matrix analysis method. As a result of modeling the processing characteristics of functional signals (at a sampling rate of 1 kHz), the system quick-response was 3 ms, with the possibility of its further decrease as its productiveness increases.

Ta witryna wykorzystuje pliki cookies do przechowywania informacji na Twoim komputerze. Pliki cookies stosujemy w celu świadczenia usług na najwyższym poziomie, w tym w sposób dostosowany do indywidualnych potrzeb. Korzystanie z witryny bez zmiany ustawień dotyczących cookies oznacza, że będą one zamieszczane w Twoim komputerze. W każdym momencie możesz dokonać zmiany ustawień dotyczących cookies

Prześlij opinię

Twoje opinie są dla nas bardzo ważne i mogą być niezwykle pomocne w pokazaniu nam, gdzie możemy dokonać ulepszeń. Bylibyśmy bardzo wdzięczni za poświęcenie kilku chwil na wypełnienie krótkiego formularza.

Formularz